This document can be found here.

















That's a long way up (gulp!)



| Octave band center frequency (hz) | Weighting |
| 31.5 | -39 |
| 63 | -26 |
| 125 | -16 |
| 250 | -9 |
| 500 | -3 |
| 1k | 0 |
| 2k | 1 |
| 4k | 1 |
| 8k | -1 |

The proposed “Adjustments to the Allowance System for Controlling HCFC Production, Import, and Export” appears to allow to EPA to go beyond the 75 percent target effective Jan. 1, 2010. The ruling also provides production allocations for various refrigerant manufacturers, ending some uncertainty in that matter.
The proposed “Ban on Sale or Distribution of Pre-Charged Appliances” says that as of Jan. 1, 2010 it will be illegal to import, produce, or sell R-22 for use in new equipment or pre-charged into such equipment. In effect, the ruling appears to say that if a contractor buys a product as of Jan. 1, 2010 that needs R-22, the charging would have to be done with existing recovered, recycled, and/or reclaimed R-22 — or R-22 alternatives — rather than virgin R-22.

For commercial installations, an ITC is provided for geothermal heat pumps equal to 10 percent of the expenditures, including allocable labor costs for facilities placed in service after October 3, 2008. There is no cap on the amount of expenditures which can be used for the credit (and no cap on the credit itself). In addition, geothermal heat pumps are eligible for Modified Accelerated Cost-Recovery which provides for depreciation over 5 years. The credit is determined by the cost of the system. However, if the equipment is financed by any subsidy program (federal, state or local) or with tax-exempt bond, the basis of the equipment must be reduced by the amount of the subsidy. Contrary to the residential credit, on commercial applications the units do not need to be Energy Star rated to apply. To collect this credit, the taxpayer would need to complete IRS Form 3468. The form will need revision by the IRS to reflect the addition of geothermal heat pumps.







| Size of Air Conditioning System tons | Gallons of Hot Water per Hour | Gallons of Hot Water per Day |
| 3 | 15-to-25 | 180-to-300 |
| 5 | 25-to-40 | 300-to-480 |
| 10 | 50-to-80 | 600-to-960 |
| 20 | 100-to-160 | 1200-to-1800 |
| 30 | 150-to-240 | 1800-to-2880 |



1412.4.1 Dampers: Outside air intakes, exhaust outlets and relief outlets serving conditioned spaces shall be equipped with motorized dampers which close automatically when the system is off or upon power failure. Stair shaft and elevator shaft smoke relief openings shall be equipped with normally open (fails open upon loss of power) dampers. These dampers shall remain closed until activated by the fire alarm system or other approved smoke detection system.
EXCEPTIONS:
- Systems serving areas which require continuous operation.
- Combustion air intakes.
- Gravity (non-motorized) dampers are acceptable in systems with a design outdoor air intake or exhaust capacity of 300 cfm or less
buildings less than 3 stories in height.Gravity (non-motorized dampers are acceptable in exhaust and relief outlets in the first story and levels below the first story of buildings three or more stories in height.Reserved- Type 1 grease hoods exhaust.
Dampers installed to comply with this section, including dampers integral to HVAC equipment, shall have a maximum leakage rate when tested in accordance with AMCA Standard 500 of:
- Motorized dampers: 10 cfm/ft2 of damper area at 1.0 in. w.g.
- Non-motorized dampers: 20 cfm/ft2 of damper area at 1.0 in. w.g., except that for non-motorized dampers smaller than 24 inches in either dimension: 40 cfm/ft2 of damper area at 1.0 in. w.g.
Dampers used as a component of packaged HVAC equipment shall comply with the damper leakage requirements, unless it is the lowest leakage available as a factory option. Drawings shall indicate compliance with this section.